You can connect 8 alarm sensors to the monitor. The number of sensors can be increased up to 16 using the SH-16 module. This menu allows you to specify pecularities and configure the operation of each sensor separately.
The table with sensor settings consists of the following parameters:
- sensor No.;
- sensor type:
- normal: the sensor is activated only when the scene (for which it is enabled) is turned on. Typically this type is used for door and window sensors;
- emergency: the sensor is active all the time, and a trigger notification is sent to the Management Software (no longer supported);
- 24 hour: the sensor is active all the time, regardless of the selected scene. This type can be selected for flood, gas, volume, smoke and heating sensors.
- sensor operation mode (cases for triggering a sensor):
- 3C is activated by any change in the position of the contacts;
- NO is for the normally open sensor, activated when the contacts are closed;
- NC is for the normally closed sensor, activated when the contacts are opened;
- Bell is for functioning in doorbell mode. When the contacts are closed, the monitor will start playing the incoming call ringtone;
- SOS call is for making a SOS call (to the number specified in the web interface or to the concierge) when the sensor contacts are closed.
activation delay time (from 0 to 60 sec) before the sensor is triggered (available when selecting a normal sensor type);
- sensor name (type) selection for additional information when triggered. There are such available options as smoke, gas, PIR, door, window, panic, flood.