Electrical connection

Electrical connection

After checking the completeness of the device, you can proceed to the connection.

To connect you will need:

  • Ethernet cable UTP cat5 or higher connected to a network switch / router.

Cable lenght recomendations

The maximum length of a UTP CAT5 cable segment must not exceed 100 meters, according to the IEEE 802.3 standard.

  • To connect the panel via PoE, you need to use a switch that works with 802.3 af support with a maximum power per port of no more than 15.4 watts.

When connecting the panel panel by PoE,it is prohibited to power the lock using panel's power. You must use a separate power supply, otherwise it may cause damage to the device.

  • Power supply at +12 Volt, 2 Ampere.

  • Wires must be brought for connecting the lock and additional modules (optional).



Below is the designation of all contacts on the panel.

Pin assignment on the outdoor panel:

 GND: Ground.

12V: Power supply + 12 Volts.

485A: RS485 Data +.

485B: RS485 Data -.

DoorA-DoorE: Controlled inputs (dry contacts). It is possible to use for connecting the exit buttons and door sensors, and fire alarm sensors as well, if connected to the corresponding bus.

GNDA-GNDE: Ground for controlled inputs.

D0: Contact Data 0 for Wiegand.

D1: Contact Data 1 for Wiegand.

GND: Ground for Wiegand.

GND: Ground for locks.

R_A_NO: Normally open contact for 1 relay.

R_A_COM: Switchable contact for 1 relay.

R_A_NC: Normally closed contact for 1 relay.

R_B_NO: Normally open contact for 2 relay.

R_B_COM: Switchable contact for 2 relay.

R_B_NC: Normally closed contact for 2 relay.

Related content

Electrical connection
Electrical connection
More like this
Electrical connection
Electrical connection
More like this
Electrical connection
Electrical connection
More like this
Electrical connection
Electrical connection
More like this
Electrical connection
Electrical connection
More like this
Electrical connection
Electrical connection
More like this